文章
  • 文章
搜索
首页 >> 公司新闻 >>新闻中心 >> 奥特多蓄电池安装直流屏柜内的布线及端子要求:
详细内容

奥特多蓄电池安装直流屏柜内的布线及端子要求:


1)奥特多蓄电池导线连接方式可以采用压接、焊接或插接,并符合其本身标准的规定;

2)所有端子的连接线必须牢固,一个端子一般只应连接一根电缆芯,不得超过2根;

3)经常移动的连接线应采用多股铜绝缘软线,并有足够长度裕度和适当的固定,以免急剧弯曲和产生过度张力;

4)凡电气原理图或接线图上有回路标号的导线端部应标出回路编号,标号应清楚、牢固、完整、不褪色;

5)设备内部接线应采用标准导线,所有接线须用防火型槽管保护,外露接线需束在一起,用适当的夹具固定或支持,水平或垂直走向;

6)设备的内部接线应在工厂完成,出厂前要进行全面检查。

7)所有导线截面应满足其负荷电流要求,并留有足够裕度的内容。

8)直流电源系统明敷电缆应选用耐火电缆或采取了规定的耐火防护措施的阻燃电缆。控制和保护回路直流电缆应选用屏蔽电缆。

9)直流柜内采用微型断路器的直流馈线应经端子排出线。

10)奥特多蓄电池组引出电缆采用单芯电力电缆。

标题10.jpg

1) The lead connection of the battery can be pressed, welded or plugged in accordance with its own standards;
2) The connecting wires of all terminals must be firm. Generally, only one cable core should be connected to one terminal, not more than two;
3) Frequent moving connecting wire should be multi-strand copper insulated flexible wire, and have sufficient length margin and appropriate fixation, so as to avoid sharp bending and excessive tension;
4) Circuit number should be marked at the end of wires with circuit number on the electrical schematic diagram or wiring diagram, and the circuit number should be clear, firm, complete and colorless;
5) The internal wiring of the equipment shall adopt standard wires, and all the wiring shall be protected by fireproof groove pipes. The exposed wiring shall be bundled together and fixed or supported with appropriate clamps, horizontally or vertically;
6) The internal wiring of the equipment should be completed in the factory, and a comprehensive inspection should be carried out before leaving the factory.
7) All wire sections should meet the load current requirements, and leave enough margin content.
8) The exposed cables of the DC power supply system shall be fire resistant cables or flame retardant cables with prescribed fire resistant protection measures. DC cables for control and protection circuits should be shielded.
9) DC feeders in the DC cabinet with miniature circuit breakers should be discharged through terminals.
10) The outlet cable of the battery group adopts single core power cable.